Description
- Remote Bulb Aquastat Controller
- Type 3/8 Inch Diameter x 2-7/8 Inch Length Copper Bulb, 66 Inch Length Capillary, Horizontal / Vertical Immersion, High Limit, Manual Reset
- Temperature Range 100 to 240 Deg F
- Maximum Temperature Rating 150 Deg F
- Contact Rating 8 Amp at 120 Volt AC / 5.1 Amp at 240 Volt AC (Full Load), 48 Amp at 120 Volt AC / 30.6 Amp at 240 Volt AC (Locked Rotor), 0.25 Amp at 0.25 to 12 Volt DC (Millivolt)
- Contact Configuration SPST, Contact Break on Temperature Rise
- Connection Type 3/4 Inch Conduit, Screw Terminal
- Application Boiler, Storage Tank
- Approval UL, CSA
- Overall Dimension 2 Inch Width x 2-1/8 Inch Depth x 5-5/8 Inch Height
- Pressure Rating 200 PSI (Capillary Bulb), 255 PSI (Immersion Well)
- Sensing Bulb Fill Liquid Toluene or Silicone Oil
- Includes Stop Factory Set at 240 Deg F